Single Core, PVC Insulated, Flexible Conductors
( H05V - K , H07V - K , NYAF )
Layers Construction
- Cu / PVC
PVC single core, non sheathed with flexible conductor for general purposes
Wire Structure
Conductor type and class:
Flexible copper conductor according to IEC 60228, class 5 (flexible)
PVC core insulation:
Compound type of PVC / C
Core insulation colors:
As per customer request
Technical Data
Temperature range:
Flexing: -5 ℃ to +70 ℃
Fixed installations: -30 ℃ to +70 ℃
Nominal Voltage Uo / U:
300 / 500 V for conductors up to and including 1 mm².
450 / 750 V for conductors above 1 mm²
Reference Standard:
ISIRI 607 – 3
IEC 60227 – 3
Wire code:
ISIRI ( 607 ) 06 for conductors up to 1 mm²
60227IEC 05 ( H05V – K )
60227IEC 02 ( H07V – K )
NYAF
Application
These types of wires are used for fixed installation as connection wires in underground ducts, machines and control panels that require flexibility.
It is not allowed to place these types of wires directly on cable trays, channels or tanks, but placing them inside the pipe and under the plaster is allowed.
Properties
Approx. Weight ( kg / km ) | Max. Conductors Resistance at 20˚C ( Ω / km ) | Average Outer Diameter ( mm ) | Nominal Insulation Thickness ( mm ) | Nominal Cross Section of Conductors ( mm2 ) | |
Min. | Max. | ||||
9 | 39 | 2.1 | 2.5 | 0.6 | 0.5 |
11 | 26 | 2.2 | 2.7 | 0.6 | 0.75 |
14 | 19.5 | 2.4 | 2.8 | 0.6 | 1 |
20 | 13.3 | 2.8 | 3.4 | 0.7 | 1.5 |
31 | 7.98 | 3.4 | 4.1 | 0.8 | 2.5 |
46 | 4.95 | 3.9 | 4.8 | 0.8 | 4 |
65 | 3.3 | 4.4 | 5.3 | 0.8 | 6 |
109 | 1.91 | 5.7 | 6.8 | 1 | 10 |
164 | 1.21 | 6.7 | 8.1 | 1 | 16 |
252 | 0.78 | 8.4 | 10.2 | 1.2 | 25 |
343 | 0.554 | 9.7 | 11.7 | 1.2 | 35 |
490 | 0. 386 | 11.5 | 13.9 | 1.4 | 50 |
679 | 0.272 | 13.2 | 16 | 1.4 | 70 |
894 | 0.206 | 15.1 | 18.2 | 1.6 | 95 |
1128 | 0.161 | 16.7 | 20.2 | 1.6 | 120 |
1409 | 0.129 | 18.6 | 22.5 | 1.8 | 150 |
1712 | 0.106 | 20.6 | 24.9 | 2 | 185 |
2256 | 0.0801 | 23.5 | 28.4 | 2.2 | 240 |